Littelfuse PGR-6130 Series Manual de usuario

Busca en linea o descarga Manual de usuario para Hardware Littelfuse PGR-6130 Series. Littelfuse PGR-6130 Series User Manual Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 1
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 0
Protection Relays & Controls
© 2013 Littelfuse Protection Relays & Controls
Littelfuse.com/pgr-6130
PGR-6130 SERIES
Electronic Overload Relay
Description
The PGR-6130 Electronic Overload Relay provides protection
for small three-phase motors up to 1,000 Vac. No current
transformers are required for currents up to 91 A. The
protective functions include overload, overtemperature, phase
unbalance, phase loss, and phase sequence. The PGR-6130
Electronic Overload Relay offers dependable protection and can
be used on pumps, conveyor belts, ventilation fans and other
small-motor applications that require standard protection.
Specifications
Protective Functions Overload (49, 51)
(IEEE Device Numbers) Phase sequence (46)
Overcurrent (51)
PTC overtemperature (49)
Unbalance (current) (46)
Phase loss (current) (46)
Input Voltage
See ordering information
Frequency 50, 60 Hz
Dimensions H 83 mm (3.3”); W 78 mm (3.1”); D 99 mm (3.9”)
Test Button Standard feature
Reset Button Standard feature
Output Contacts Isolated Form A and Form B
Approvals UL Listed (E343314), CE (European Union)
Warranty 5 years
Mounting DIN
ORDERING NUMBER CONTROL POWER FULL-LOAD CURRENT
PGR-6131-24 24 Vdc 4-16.7 A
PGR-6131-120 120 Vac 4-16.7 A
PGR-6131-240 240 Vac 4-16.7 A
PGR-6132-24 24 Vdc 15-40.5 A
PGR-6132-120 120 Vac 15-40.5 A
PGR-6132-240 240 Vac 15-40.5 A
PGR-6133-24 24 Vdc 40-91 A
PGR-6133-120 120 Vac 40-91 A
PGR-6133-240 240 Vac 40-91 A
Motor Protection–Electronic Overload (PGR 6000 Family)
Ordering Information
NOTE: External CTs can be used for full-load currents >91 A.
FEATURES BENEFITS
No CTs required
No current transformers required for currents up to
91 A, simplifies installation and reduces cost
Adjustable
trip settings
Adjustable overload trip class setting from 5 to 35
to match motor characteristics
Output contacts
Form A and Form B ground-fault output contacts for
operation of separate annunciation and trip circuits
Remote indication
Allows remote cause-of-trip indication and reset
Overload
Extends motor life and prevents insulation failures
and fires
Phase loss/Phase
sequence
Detects unhealthy supply conditions
Unbalance (current)
Prevents overheating due to unbalanced phases
PTC overtemperature
Detect high ambient or blocked ventilation and
single phasing; prevents shaft/pump damage
Features & Benefits
PGB-6130 Remote Indication
and Reset Assembly
Optional remote indication of overcurrent,
phase unbalance, phase loss, phase sequence
and overtemperature. Remote reset included.
Accessories
A
ACCESSORIES REQUIREMENT
PGB-6130 Optional
PGR-6130 SERIES
(Electronic Overload Relay)
PGB-6130
(Remote Indication
and Reset Assembly)
PTC
M
L2
L1
Simplified Circuit Diagram
A
Rev: 4-A-050213
Based on Manual Rev 0
Vista de pagina 0
1

Indice de contenidos

Pagina 1 - PGR-6130 SERIES

Protection Relays & Controls© 2013 Littelfuse Protection Relays & Controls Littelfuse.com/pgr-6130PGR-6130 SERIESElectronic Overload RelayDesc

Comentarios a estos manuales

Sin comentarios